Page:Current Strategies for Engineering Controls in Nanomaterial Production and Downstream Handling Processes.pdf/75

From Wikisource
Jump to navigation Jump to search
This page has been proofread, but needs to be validated.

Table 5. Comparison of the fume hood performance test methods

Test method Invent-UK DIN 12924 BS 7258 EN 14175:2003 ANSI/ASHRAE 110-1995
Country United Kingdom Germany Great Britain European Union United States
Test parameters Face velocity Tracer gas test Tracer gas test Face velocity Face velocity and cross draft
Tracer gas test Tracer gas test Smoke visualization
Robustness test (dynamic test by walk-bys and traffic) Tracer gas test
Tracer gas 10% SF6[1] + 90% N2 @ 3.0 LPM 10% SF6 + 90% N2 @ 3.33 LPM 10% SF6 + 90% N2 @ 2.0 LPM 10% SF6 + 90% N2 @ 2-4 LPM 100% SF6 @ 4.0 LPM
Tracer gas sampling probes 9 20 Multi-probes depending on opening size Multi-probes (inner and outer grids) 1 in breathing zone
Use of manikin No Yes No No No


  1. Sulfur hexafluoride

60

Current Strategies for Engineering Controls in Nanomaterial Production and Downstream Handling Processes